6-12 Using the 1769-SDN Scanner Module with CompactLogix Controllers
The scanner does not yet have a profile so you must use the Generic
Profile to configure it. After you right click on the CompactBus Local
and choose New Module, click on the Generic 1769 Module, then
click OK. The following screen appears:
From the Generic Profile screen, enter a name for the scanner and
choose Data – INT for the Comm Format. Then enter the following
for the number of input, output and configuration words:
Once all values are entered, click Finish. The I/O modules should
now all appear below the CompactBus Local in the controller
organizer.
Table 6.4 Comm Format Data
Data Assembly Instance Size
Input 101 80
Output 100 5
Config 102 0