Rockwell Automation Publication 8720MC-RM001K-EN-P - September 2018 67
Connect the 8720MC-RPS Unit Chapter 5
Sequence Signal Wiring
Sequence output signals are provided from the sequence signal terminal block
(TB3) of the regulator board to indicate the unit status.
Follow these guidelines when installing sequence signal wiring:
Use twisted pair cable of 0.2…0.5 mm
2
(22…20 AWG) for the signal
line.
Separate the sequence signal wiring from the power wiring (main power
supply wiring, control power wiring, and DC-bus power wiring). Failure
to observe this precaution could result in damage to the 8720MC-RPS
unit.
Use a separate (dedicated) wireway for the sequence signal wiring.
Do not route the sequence signal wiring near any equipment that
produces electromagnetic interference.
Figure 32 - Typical Sequence Control Signal Connections
Terminal Block TB3 on Regulator Board
Load Equipment
RST
PWR
0V
24V
COM
0VC
IP
IP
RDY
RDY
2.2K
MC
1K
2.2K
1K
2.2K
1K
+VC
4.64K
4.64K
4.64K
FR
To an external error detection sequence circuit.
FR
8720MC-RPS Unit