82 Rockwell Automation Publication 8720MC-RM001K-EN-P - September 2018
Chapter 6 8720MC-RPS Startup and Operation
4. Press until the value becomes
650.
Pressing
decrements the value
on the display. Holding down the
key increases the scroll speed. If you
wish to increase the set value, press the
key.
5. Press ENT.
The set value is decided and is
written to the EEPROM. After
pressing the ENT key, the display
returns to the first User parameter
(U.000), indicating that the set
value has been decided.
6. Press PRG.
The display shows U.–––, which indicates that you can access the user
parameters.
7. Press PRG.
The operation panel returns to
Monitor mode, and the display
indicates the input current, with
the A status indicator turned ON.
This display shows that the input
current is 5 A.
8. Press .
The display shows the AC input
power voltage and the V status
indicator turns ON. This display
shows that the input power voltage
is 412V.
9. Press .
The display indicates the DC-bus
voltage and the V status indicator
turns ON. Verify that the DC-bus
voltage is almost the same as the
reference value (U.000).