21-2 Communications Instructions
storage area that keeps track of messages that have not been allocated a
buffer. The queue operates as a first-in first-out (FIFO) storage area. The
first message request stored in the queue is the message that is allocated a
buffer as soon as a buffer becomes available. The queue can
accommodate all MSG instructions in a ladder program.
When a message request in a buffer is completed, the buffer is released
back to the system. If a message is in the queue, that message is then
allocated a buffer. At that time, the data associated with the message is
read from within the controller.
The buffer and queue mechanisms are completely automatic. Buffers are
allocated and released as the need arises, and message queuing occurs if
buffers are full.
The controller initiates read and write messages through available
communication channels when configured for the following protocols:
DH-485
DF1 Full-Duplex
DF1 Half-Duplex Slave
For a description of valid communication protocols, see Protocol
Configuration on pag eE-1.
NOTE
If a message instruction was in the queue, the data that is
actually sent out of the controller may be different than
what was present when the message instruction was first
processed.

Table of Contents

Other manuals for Allen-Bradley MicroLogix 1200

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley MicroLogix 1200 and is the answer not in the manual?

Allen-Bradley MicroLogix 1200 Specifications

General IconGeneral
SeriesMicroLogix 1200
TypeProgrammable Logic Controller (PLC)
MountingDIN rail or panel mount
Programming LanguageLadder Logic
Programming SoftwareRSLogix 500
I/O PointsUp to 40
Communication PortsRS-232, RS-485
Memory6 KB user memory
Power Supply24V DC or 120/240V AC
ExpansionSupports expansion I/O modules
Operating Temperature0°C to 55°C (32°F to 131°F)
Dimensions90 mm x 110 mm
Weight0.5 kg (1.1 lbs)

Related product manuals