2-14 Configuring Your RS-232 ASCII Module
Sequential
AutoAddress
29 Get Sequential
AutoAddress will
reassign the node
address of every
module to the right.
Each module will
change its node
address to one
greater than its
neighbor. Make sure
the node address of
this module is the
desired value before
issuing this
command. When the
command is set,
each module to the
right will get a new
address one greater
than its neighbor.
0 = Do Nothing
1 = Sequential
Address
Do Nothing 0 USINT
Broadcast Baud
Rate
30 Get This command will
change the baud
rate of this and
every module to the
right to the value
indicated. If
AutoBaud is
ENABLED, this
command will not
change the
operation of the
module at power up.
0 = Do Nothing
1 = 125k Hz
2 = 250k Hz
3 = 500k Hz
Do Nothing 0 USINT
Broadcast AutoBaud 31 Get This command will
change the
AutoBaud attribute
of this and every
module to the right
to the value
indicated. If
AutoBaud is
disabled, the Baud
Rate parameter will
set the baud rate the
next time the
module is powered
up.
0 = Do Nothing
1 = Enable
2 = Disable
Do Nothing 0 USINT
Table 2.3 Parameter List
Parameter Parameter
Instance
Access Description Parameter Choices Default
Setting