Publication 1734-UM009A-EN-P - June 2002
Configuring Your RS-232 ASCII Module 2-17
Setting Up and Using the Swap Bytes Mode
This option may be helpful if the 1734-232ASC module is connected to
a DeviceNet scanner that organizes the data string characters into data
type elements that are larger than 1 byte each (i.e. SLC500). In such
cases, the bytes of the data in the masters memory organization can
be reversed from the order in which they are sent or received on the
DeviceNet and the serial link to the ASCII device. This may cause
errors in some cases. Thus, the received string ABCDEFGH may
appear in memory as BADCFEHG for 2-byte word organization, and
DCBAHGFE for 4-byte word organization.
Transmit Byte Swapping
By setting Parameter 21 (class Fhex, instance 21, attribute 1), the bytes
from the master will be swapped by the 1734-232ASC module before
transmitting the string to the ASCII device.
Receive Byte Swapping
By setting Parameter 11 (class Fhex, instance 11, attribute 1), the
1734-232ASC module will re-order the bytes received from your ASCII
device before sending the string to the master.
Maximum Number of Receive Characters Parameter Rules for Usage
Swap Bytes Mode is set for transmit and receive independently.
The byte swapping works best if the max RX and TX lengths are
multiples of the byte-swap size.