Publication 1734-UM009A-EN-P - June 2002
2-20 Configuring Your RS-232 ASCII Module
Explicit Messages to Receive the Serial Data String
Parameters 14, 15, and 16 contain the status of the most recent
incoming serial data string. You can use the data to read your devices
ASCII data via the explicit messaging technique.
Parameter 14 holds the most recent received data. Parameter 15
defines the size (in bytes) of the DeviceNet message to be sent by the
1734-232ASC module to the master. Parameter 16 holds the transaction
ID of the data string in Parameter 14 if the Header option is selected.
Status Byte Description
The Serial Status byte is an ORd bit field of a number of status and
exception flags.
TX Buffer Overflow (Bit 0)
The transmit queue has overflowed resulting in a loss of data. The
transmit I/O is full of data waiting to be transmitted. Some of the data
added has been lost. When space becomes available in the TX, this bit
will be reset.
RX Buffer Overflow (Bit 1)
The receive queue has overflowed resulting in a loss of data. The
receive is full of data waiting to be processed. The data has been lost.
When space becomes available in the RX, this bit will be reset.
IMPORTANT
You must upload this data from the 1734-232ASC
module to view current information or put your
RSNetWorx for DeviceNet into Monitor Mode.
Table 2.7 Serial Status Byte
Bit Exception
0 TX Buffer Overflow
1 RX Buffer Overflow
2 RX Parity Error
6 Handshake Error
7 New Data Flag

Table of Contents