3-12 Programming and Parameters
Basic Program Group (continued)
P040 [Decel Time 1] Related Parameter(s): P038, P039, A051, A052, A068, A070-A073
Sets the rate of deceleration for all speed decreases.
Values Default 10.0 Secs
Min/Max: 0.1/600.0 Secs
Display: 0.1 Secs
Maximum Freq
Decel Time
Decel Rate
=
Speed
0
Time
P035 [Maximum Freq]
P039 or A067
[Accel Time x]
P040 or A068
[Decel Time x]
0
Acceleration
D
eceleration
P041 [Reset To Defalts]
Stop drive before changing this parameter.
Resets all parameter values to factory defaults.
Options 0 “Idle State” (Default)
1 “Reset Defaults” After the reset function is complete, this parameter will set
itself back to “0”.
Causes an F48 Params Defaulted
fault.
P043 [Motor OL Ret] Related Parameter(s): P033
Enables/disables the Motor Overload Retention function. When Enabled, the value held in the motor
overload counter is saved at power-down and restored at power-up. A change to this parameter
setting resets the counter.
Options 0 “Disabled” (Default)
1 “Enabled”