PowerFlex 700 Adjustable Frequency AC Drive Quick Start 25
INPUTS & OUTPUTS
Digital Inputs
361
362
363
364
365
366
[Digital In1 Sel]
[Digital In2 Sel]
[Digital In3 Sel]
[Digital In4 Sel]
[Digital In5 Sel]
[Digital In6 Sel]
(11)
Selects the function for the digital inputs.
(1)
Speed Select Inputs.
To access Preset Speed 1, set [Speed
Ref x Sel] to “Preset Speed 1”.
Type 2 Alarms - Some digital input
programming may cause conflicts
that will result in a Type 2 alarm.
Example: [Digital In1 Sel] set to “5,
Start” in 3-wire control and [Digital
In2 Sel] set to 7 “Run” in2-wire.
Refer to User Manual for information
on resolving this type of conflict.
(2)
Vector Control Option Only.
Default:
Default:
Default:
Default:
Default:
Default:
Options:
4
5
18
15
16
17
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15-17
18
19
20
21
22
23
24
25
26
27
28
29
30
31-33
34
“Stop – CF”
“Start”
“Auto/ Manual”
“Speed Sel 1”
“Speed Sel 2”
“Speed Sel 3”
“Not Used”
“Enable”
(8)(10)
“Clear Faults”(CF)
(4)
“Aux Fault”
“Stop – CF”
(5)(10)
“Start”
(5)(9)
“Fwd/ Reverse”
(5)
“Run”
(6)(10)
“Run Forward”
(6)
“Run Reverse”
(6)
“Jog”
(5)
“Jog1”
(2)(5)
“Jog Forward”
“Jog Reverse”
“Stop Mode B”
“Bus Reg Md B”
“Speed Sel 1-3”
(1)
“Auto/ Manual”
(7)
“Local”
“Acc2 & Dec2”
“Accel 2”
“Decel 2”
“MOP Inc”
“MOP Dec”
“Excl Link”
“PI Enable”
“PI Hold”
“PI Reset”
“Pwr Loss Lvl”
“Precharge En”
“Spd/Trq Sel1-3”
(2,3)
“Jog 2”
(2)
100
156
162
096
140
194
380
384
388
124
(4)
When [Digital Inx Sel] is set to option 2 “Clear Faults” the Stop button cannot
be used to clear a fault condition.
(5)
Typical 3-Wire Inputs - Requires that only 3-wire functions are chosen.
Including 2-wire selections will cause a type 2 alarm.
(6)
Typical 2-Wire Inputs - Requires that only 2-wire functions are chosen.
Including 3-wire selections will cause a type 2 alarm.
(7)
Auto/Manual - Refer to “Reference Control” in the User Manual for details.
(8)
Opening an “Enable” input will cause the motor to coast-to-stop, ignoring any
programmed Stop modes.
(9)
A “Dig In ConflictB” alarm will occur if a “Start” input is programmed without a
“Stop” input.
(10)
Refer to the Sleep-Wake Mode Attention statement in the User Manual.
(11)
A dedicated hardware enable input is available via a jumper selection. Refer
to page 13 for further information.
File
Group
No.
Parameter Name & Description Values
Related
3 2 1 Auto Reference Source
0
0
0
0
1
1
1
1
0
0
1
1
0
0
1
1
0
1
0
1
0
1
0
1
Reference A
Reference B
Preset Speed 2
Preset Speed 3
Preset Speed 4
Preset Speed 5
Preset Speed 6
Preset Speed 7
(3)
3 2 1 Spd/Trq Mode
0
0
0
0
1
1
1
1
0
0
1
1
0
0
1
1
0
1
0
1
0
1
0
1
Zero Torque
Spd Reg
Torque Reg
Min Spd/Trq
Max Spd/Trq
Sum Spd/Trq
Absolute
Zero Trq