Supplemental Drive Information A-9
Table A.B 240 Volt AC Input Protection Devices (See page A-13 for Notes)
Drive
Catalog
Number
Frame
HP
Rating
PWM
Freq. Temp.
Input
Ratings Output Amps
Dual
Element Time
Delay Fuse
Non-Time
Delay Fuse
Circuit
Breaker
(3)
Motor
Circuit
Protector
(4)
140M Motor Starter with Adjustable Current
Range
(5)(6)
ND HD kHz °C Amps kVA Cont. 1 Min. 3 Sec. Min.
(1)
Max.
(2)
Min.
(1)
Max.
(2)
Max.
(8)
Max.
(8)
Available Catalog Numbers - 140 . . .
(7)
240 Volt AC Input
20BB2P2 0 0.5 0.33 4 50 1.7 0.7 2.2 2.4 3.3 3 6 3 10 15 3 M-C2E-B25 M-D8E-B25 – –
20BB4P2 0 1 0.75 4 50 3.3 1.4 4.2 4.8 6.4 5 8 5 15 15 7 M-C2E-B63 M-D8E-B63 – –
20BB6P8 1 2 1.5 4 50 5.9 2.4 6.8 9 12 10 15 10 25 25 15 M-C2E-C10 M-D8E-C10 M-F8E-C10 –
20BB9P6 1 3 2 4 50 8.3 3.4 9.6 10.6 14.4 12 20 12 35 35 15 M-C2E-C10 M-D8E-C10 M-F8E-C10 –
20BB015 1 5 3 4 50 13.7 5.7 15.3 16.8 23 20 30 20 60 60 30 M-C2E-C16 M-D8E-C16 M-F8E-C16 –
20BB022 1 7.5 5 4 50 19.9 8.3 22 24.2 33 25 50 25 80 80 30 M-C2E-C25 M-D8E-C25 M-F8E-C25 -CMN-2500
20BB028 2 10 7.5 4 50 25.7 10.7 28 33 44 35 60 35 100 100 50 – – M-F8E-C32 -CMN-4000
20BB042 3 15 10 4 50 38.5 16.0 42 46.2 63 50 90 50 150 150 50 – – M-F8E-C45 -CMN-6300
20BB052 3 20 15 4 50 47.7 19.8 52 63 80 60 100 60 200 200 100 – – – -CMN-6300
20BB070 4 25 20 4 50 64.2 26.7 70 78 105 90 150 90 275 275 100 – – – -CMN-9000
20BB080 4 30 25 4 50 73.2 30.5 80 105 140 100 180 100 300 300 100 – – – -CMN-9000
20BB104 5 40 – 4 50 98 40.6 104 115 175 125 225 125 400 300 150 – – – –
– 30 4 50 73 30.5 80 120 160 100 175 100 300 300 100 – – – -CMN-9000
20BB130 5 50 – 4 50 122 50.7 130 143 175 175 275 175 500 375 250 – – – –
– 40 4 50 98 40.6 104 156 175 125 225 125 400 300 150 – – – –
20BB154 6 60 – 4 50 145 60.1 154 169 231 200 300 200 600 450 250 – – – –
– 50 4 50 122 50.7 130 195 260 175 275 175 500 375 250 – – – –
20BB192 6 75 – 4 50 180 74.9 192 211 288 225 400 225 600 575 250 – – – –
– 60 4 50 145 60.1 154 231 308 200 300 200 600 450 250 – – – –