1-26 Installation/Wiring
General Notes (continued)
• More information regarding harmonic emissions can be found in the
PowerFlex 70/700 Reference Manual (publication PFLEX-RM001).
• When operated on a public supply system, it is the responsibility of
the installer or user to ensure, by consultation with the distribution
network operator and Rockwell Automation, if necessary, that
applicable requirements have been met.
Essential Requirements for CE Compliance
Conditions 1-6 listed below must be satisfied for PowerFlex drives to
meet the requirements of EN61800-3.
1. Standard PowerFlex 700 CE compatible Drive.
2. Review important precautions/attention statements throughout this
manual before installing the drive.
3. Grounding as described on page 1-4
.
4. Output power, control (I/O) and signal wiring must be braided,
shielded cable with a coverage of 75% or better, metal conduit, or
equivalent attenuation.
5. All shielded cables should terminate with the proper shielded
connector.
6. Conditions in Table 1.I
.
Table 1.I PowerFlex 700 EN61800-3 EMC Compatibility
Frame
Second Environment (Industrial)
(1)(2)
External filter Not Required if motor
cables are restricted to design shown
(1)
Motor cable limited to 30 m (98 ft.) for installations in the second (industrial)
environment without additional external line filters.
(2)
Refer to the PowerFlex 70/700 Reference Manual for installations in the first
(residential) environment and installations in the second environment with motor
cables longer than 30 m (98 ft.).
First Environment
Restricted Distribution
Any Drive and Option
0-6 Restrict Motor Cable to 30 m (98 ft.)
(2)