2-96 Motor Nameplate
Motor Nameplate [Motor NP Volts]
The motor nameplate base voltage defines the output voltage, when
operating at rated current, rated speed, and rated temperature.
[Motor NP FLA]
The motor nameplate defines the output amps, when operating at rated
voltage, rated speed, and rated temperature. It is used in the motor thermal
overload, and in the calculation of slip.
[Motor NP Hz]
The motor nameplate base frequency defines the output frequency, when
operating at rated voltage, rated current, rated speed, and rated temperature.
[Motor NP RPM]
The motor nameplate RPM defines the rated speed, when operating at
motor nameplate base frequency, rated current, base voltage, and rated
temperature. This is used to calculate slip.
[Motor NP Power]
The motor nameplate power is used together with the other nameplate
values to calculate default values for motor parameters to and facilitate the
commissioning process. This may be entered in horsepower or in kilowatts
as selected in the previous parameter or kW for certain catalog numbers and
HP for others.
[Motor NP Pwr Units]
The rated power of the motor may be entered in horsepower or in kilowatts.
This parameter determines the units on the following parameter.