EasyManua.ls Logo

Allen-Bradley PowerMonitor 500

Allen-Bradley PowerMonitor 500
90 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
40 Rockwell Automation Publication 1420-UM001E-EN-P - March 2016
Chapter 4 Communication
2. Click the Communication tab and enter the path and method.
3. Click OK to complete message setup.
Implicit Messaging - Generic Ethernet Module Input Data Connection
The PowerMonitor 500 unit with EtherNet/IP communication supports Class 1
connections to its nine Assembly Instances. To configure a Class 1 connection to
a selected Assembly Instance with a Logix controller, follow these steps.
1. Open the controller program offline in the Logix Designer application (or
online in Program mode if you are using a ControlLogix® controller).
2. In the I/O configuration tree, right-click the Ethernet communication
module (for example, 1756-EN2T), and choose New Module.
3. From the Communication pull-down menu, choose ETHERNET-
MODULE Generic Ethernet Module.
Path Method
<Ethernet Module, Port (always 2 for Ethernet), Power Monitor IP Address> CIP

Related product manuals