Terminal Overview 1-35
Alarm List
PanelView terminals support an Alarm List queue to store information
on triggered alarms. The Alarm List stores a maximum of 100 alarms
or as many as the terminal can hold in nonvolatile RAM. The number
of alarms stored in the list is configured using the PanelBuilder32
software.
The Alarm List stores the following data for each alarm:
acknowledge indicator
alarm date and time
acknowledge date and time
alarm trigger value
alarm text including variables
The Alarm List is cleared:
when an application is downloaded to the terminal
when the terminal is reset or power is cycled
The Alarm List object may appear on the Alarm Banner or other
application screens. The data that displays in the Alarm List is
configured using the PanelBuilder32 Software.