3-12 Configuring the Terminal
Active Baud (read only)
Displays the current baud rate of the PanelView terminal. The new
baud is displayed after a reset. If the baud rate was set to AutoBaud,
active baud displays the rate set by the terminal. If the baud rate was
set to PGM, the active baud displays the most recent baud stored on
the communications card.
Bus-off Interrupt
Specifies what occurs when a CAN bus-off interrupt occurs on the
DeviceNet network. The PanelView is not allowed network access
when Hold on Reset is selected and a Bus-off Interrupt occurs.
Hold in Reset holds the PanelView and waits for a
communications reset or a terminal reset.
Reset and Continue Communications resets DeviceNet
communications and re-establishes the communications link.
Interscan Delay
Opens the numeric entry scratchpad so you can change the delay
between scans of the Explicit-Client tags. Enter a value of 0 to 65535
milliseconds and press the Enter
key. (On touch screen terminals,
press the
key on the scratchpad.) The default is 500 milliseconds.
This time delay is inserted between each full scan of the
Explicit-Client tags in the current screen context. The value is initially
set by the downloaded application but can be changed by an
operator. The new value takes effect at the end of the current scan
delay.
Explicit-Client mode will generate low priority, network messaging at
intervals less than 500 milliseconds.
Input Size
Displays the number of words (0 to 64) sent by the PanelView in an
I/O message. The default value is 0, which indicates that no input data
is exchanged with the scanner. This value is set by the downloaded
application.
Output Size
Displays the number of words (0 to 64) received by the PanelView in
an I/O message. The default value is 0, which indicates no output data
is exchanged with the scanner. This value is set by the downloaded
application.
Comm LED
solid fill - normal operating state
blinking - no communications established
no fill - hardware failure
Exit
Returns to the Configuration Mode menu.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley PV300 Micro and is the answer not in the manual?

Allen-Bradley PV300 Micro Specifications

General IconGeneral
BrandAllen-Bradley
ModelPV300 Micro
CategoryTouch terminals
LanguageEnglish

Related product manuals