3-14 Configuring the Terminal
Node
Specifies the node number (0 - 254 decimal) for DF1 network
communications. For point-to-point communications with an SLC,
PLC, MicroLogix or a 1761-NET DNI module, the default node number
of 64 is used.
When you press F4, the numeric entry scratchpad opens. Enter a node
number and press the Enter
key. (On touch screen terminals, press
the
key on the scratchpad.)
Handshaking
Specifies the type of handshaking used by the RS-232 port.
On (CTS/RTS enabled)
OFF (CTS/RTS disabled)
Press F5 or touch the box to select an option. The default is Off.
Comm LED
solid fill - normal operating state
blinking - no communications established with logic controller
no fill - hardware failure
Fault LED
no fill - normal operating state
blinking - hardware is functioning but an application is not
loaded or the current application is corrupted.
Exit
Returns to the Configuration Mode menu.