Translated from the original language - English - 33Manual 6-1624970M - rev. 1 - 11/01/2023
STANDARD LEARNING
With standard learning, the control unit performs all the procedure and the calculation of slowdowns, which will be set with the same
amplitude both in opening and closing ( see basic parameter " Lsi").
DANGER
• Check that during the first movement the display displays "LOP" and the gate moves in the OPENING
DIRECTION.
If necessary, press the DOWN button and then the SS button to reverse the movement.
• In order for the automation and all the safety devices installed to function correctly, it is
necessary to verify the correct direction of the automation movement.
NOTE
• If the procedure starts while the limit switches are active, or if a safety device is involved during movement,
the procedure is stopped and the words " L-- " appear on the display.
Carry out the appropriate checks and press the SS button to resume learning from step 3.
1.
Unlock the transmission of the motor and manually bring the gate in
mid-stroke.
Then insert the motor transmission again.
2.
Press the UP button and the MENU button simultaneously for at least
5 seconds until the display shows " LOP ".
At this stage the gear motor moves in search of the opening limit
switch.
Verify that the automation moves in the opening direction.
SS
3.
Once the opening limit switch has been reached, the automation
automatically moves in closing, at low speed, until the closing limit
switch is reached. At this stage the display shows " LCL ".
4.
Once the closing limit switch has been reached, the automation
automatically moves in opening, at low speed, until the opening limit
switch is reached. At this stage the display shows " LOP ".
5.
Once the opening limit switch has been reached, the automation
moves in closing at full speed and with the slowdowns set by the
menu through the " Lsi "parameter.
6.
After the procedure the control unit displays "Ldone"