36 - English - Translated from the original language Manual 6-1624970M - rev. 1 - 11/01/2023
Obstacle sensitivity on full speed movement
NOTE
• Too high a level of sensitivity could cause an abnormal behaviour of the automation depending on the force
that the gear motor needs to move the automation.
• Adjust this parameter according to current regulations.
Set the sensitivity level for the impact sensor to intervene during gate movement.
The impact sensor controls a short reversal of movement to free the obstacle.
PARAMETER VALUES DEFAULT
SEn
OFF = disabled.
From 1 to 100 %
30 %
Obstacle sensitivity on slow speed movement
NOTE
• Too high a level of sensitivity could cause an abnormal behavior of the automation depending on the force
that the gear motor needs to move the automation.
• Adjust this parameter according to current regulations.
Set the sensitivity level to make the impact sensor intervene during the movement of the gate during slowdown.
The impact sensor intervention during slowdown controls a short reversal of the movement to free the obstacle.
PARAMETER VALUES DEFAULT
SEL
OFF = disabled.
From 1 to 100 %
50 %
Normal Speed
Set the speed of the motor movement during the normal speed area.
This value is expressed as a frequency.
PARAMETER VALUES DEFAULT
SPn
From 30 to 100 Hz 50 Hz
Slowdown Speed
Set the speed of the motor movement during the slowdown area.
This value is expressed as a percentage of the "Normal Speed".
Changing the parameter "Normal Speed" also aects the parameter "Slowdown Speed".
PARAMETER VALUES DEFAULT
SPL
From 20 to 40 % of SPn 30 % of SPn
Configuration of the STEP-BY-STEP function
NOTE
• By setting the CONDOMINIUM functionality you must set an automatic closing time to make the gate close.