Error Diagnosis / Error messages
No. Display Description Remedy
701 Error low pressure.
Please call AS
Low pressure pressostat or low-pressure sensor in the cooling
circle has responded (L/W) or for longer than 20 seconds (S/W).
Check HP for leakage, switching point
pressure state, defrosting and T-outd.min.
702 Low pressure stop
RESET autom.
Only possible for L/W devices: Low pressure in the cooling circle
has responded. After some time, automated HP restart.
Check HP for leakage, switching point
pressure state, defrosting and T-outd.min.
703 Antifreeze
Please call tter
Only possible for L/W devices: If the heat pump is running and
the temperature in ow is < 5 °C, antifreeze is detected.
Check HP power, defrost valve and heating
system.
704 Error hot gas
Reset in hh:mm
Maximum temperature in the hot gas cooling circle exceeded.
Automatic HP restart after hh:mm.
Check coolant quantity, evaporation,
overheating ow, return and HS-min.
705 Motor protection VEN
Please call tter
Only possible for L/W devices: Motor protection has responded. Check set value and ventilator / BCP.
706 Motor protection BCP
Please call tter
Option only possible for S/W- or W/W devices Motor protection
of the brine or well water circulating pump or the compressor
has responded.
Check set values, compressor, BOS.
707 Coding of HP
Please call tter
Break or short-circuit of the coding bridge in HP after the rst
switch-on.
Coding resistance in HP, check plug and
connection line.
708 Return sensor
Please call tter
Break or short-circuit in the return sensor. Check return sensor, plug and connection
line.
709 Flow sensor
Please call tter
Break or short-circuit in the ow sensor No fault shutdown for
S/W- or W/W devices.
Check ow sensor, plug and connection
line.
710 Hot gas sensor
Please call tter
Break or short-circuit in the hot gas sensor of the cooling circle. Check hot gas sensor, plug and connection
line.
711 External temp. sensor
Please call tter
Break or short-circuit in the external temperature sensor No
fault shutdown. Fixed value to -5 °C.
Check external temperature sensor, plug
and connection line.
712 Domestic hot water sensor.
Please call tter
Break or short-circuit in the domestic hot water sensor No fault
shutdown.
Check domestic hot water sensor, plug and
connection line.
713 HS-on sensor
Please call tter
Break or short-circuit in the heat source sensor (inlet). Check heat source sensor, plug and
connection line.
714 Hot gas SW
Reset in hh:mm
Check thermal application limit of the HP. Domestic hot water
o for hh:mm.
Fault only triggers if the compressor is running.
Check ow of domestic hot water, heat
exchanger, domestic hot water temperature
and circulation pump.
715 High-pressure switch-o
RESET autom.
High pressure in the cooling circle has responded. After some
time, automated HP restart.
Check ow of HW, overows, temperature
and condensation.
716 High-pressure fault
Please call tter
High pressure pressostat in the cooling circle has responded
several times.
Check ow of HW, overows, temperature
and condensation.
717 Flow HS
Please call tter
Flow switch for W/W devices has responded during the pre-
rinsing time or operation.
Check ow, switching point for DFS, lter,
air clearance.
718 Max. outside temp.
RESET autom. in hh:mm
Only possible for L/W devices: Outside temperature has
exceeded permissible maximum value. Automatic HP restart
after hh:mm.
Check outside temperature and set value.
719 Min. outside temp.
RESET autom. in hh:mm
Only possible for L/W devices: Outside temperature has fallen
below the permissible minimum value. Automatic HP restart
after hh:mm.
Check outside temperature and set value.
720 HS temperature
RESET autom. in hh:mm
Option only possible for S/W- or W/W devices Temperature at
evaporation outlet has fallen below the safety value on the HS
side several times. Automatic HP restart after hh:mm.
Check ow, lter, air clearance, temperature.
721 Low-pressure switch-o
RESET autom.
Low pressure pressostat or low-pressure sensor in the cooling
circle has responded. After some time, automated HP restart
(S/W and W/W).
Check switching point of the pressostat,
ow on HS side.
722 Tempdi HW
Please call tter
Temperature spread in the heating mode is negative
(=erroneous).
Check function and location of the ow and
return sensor.
723 Tempdi SW
Please call tter
Temperature spread in the domestic hot water mode is
negative (=erroneous).
Check function and location of the ow and
return sensor.