P54x/EN ST/La4 Settings
(ST) 4-90
MiCOM P543, P544, P545, P546
ST
Setting range
Menu text Default setting
Min. Max.
size Step
Fn. Key 2 to 10
Status
Unlock/Enable Disable, Lock, Unlock/Enable
Setting to activate function key. The ‘Lock
to toggle mode to be locked in its current ac
setting allows a function key output that is set
tive position.
Fn. Key 2 to 10
Mode
Toggle Toggle, Normal
Sets the function key in or norm de. In le’ mode, a sing press will
is
n
ssed.
toggle al mo ‘Togg le key
set/latch the function key output as ‘high’ or ‘low’ in programmable scheme logic. Th
feature can be used to enable/disable relay functions. In the ‘Normal’ mode the functio
key output will remain ‘high’ as long as key is pre
Fn. Key 2 to 10 Label Function Key 2 to 10
Allows the text of the function key to be changed to something more suitable for the
application.
1.4.14 I for IEC
T TOR column are mostly data cells, displayed for
i t edita order to edit nfigura neces to use the IED
C io.
Se ge
ED configurator ( 61850 configuration)
he contents of the IED CONFIGURA
nformation but no ble. In the co tion, it is sary
onfigurator tool within MiCOM S1 Stud
tting ran
Menu text Default setting Step size
Min. Max.
IED CONFIGURATOR
Switch Conf.Bank No Action No Action, Switch Banks
Setting which allows the r to switch betwe ration d in the Active
and held in the
use en the current configu , hel
Memory Bank (and partly displayed below), to the configuration sent to
Inactive Memory Bank.
Active Conf.Name Data
The name of the configuration in the Active Memory Bank, usually taken from the SCL file.
Active Conf.Rev Data
Configuration Revision number of the configuration in the Active Memory Bank, usually
taken from the SCL file.
Inact.Conf.Name Data
The name of the configuration in the Inactive Memory Bank, u
file.
sually taken from the SCL
Inact.Conf.Rev Data
Configuration Revision number of the configuration in the Inactive Memory Bank, usually
SCL file. taken from the
IP PARAMETERS
IP Address Data
Displays the unique network IP address that identifies the relay.
Subnet Mask Data
Displays the sub-networ onnek that the relay is c cted to.
Gateway Data
Displays the IP address of the gateway (proxy) that the relay is connected to, if any.