Measurements and Recording P54x/EN MR/La4
MiCOM P543, P544, P545 & P546
(MR) 8-13
MR
Menu text Default settings Available settings
MEASUREMENT SETUP
Fix Dem. Period 30 minutes 1 to 99 minutes step 1 minute
This setting defines the length of the fixed demand window.
Roll Sub Period 30 minutes 1 to 99 minutes step 1 minute
These two settings are used to set the length of the window used for the calculation of
rolling demand quantities.
Num. Sub Periods 1 1 to 15 step 1
This setting is used to set the resolution of the rolling sub window.
Distance Unit* km km/miles
This setting is used to select the unit of distance for fault location purposes, note that the
length of the line is preserved when converting from km to miles and vice versa.
Fault Location* Distance Distance/Ohms/% of Line
The calculated fault location can be displayed using one of several options selected using
this setting.
Remote2 Values Primary Primary or Secondary
The setting defines whether the values measured via the 2
nd
Rear Communication port are
displayed in primary or secondary terms.
1.4.8 Measurement display quantities
There are four Measurement columns available in the relay for viewing of measurement
quantities. These can also be viewed with MiCOM S1 Studio (see MiCOM Px40 - Monitoring
section of the MiCOM S1 Studio User Manual) and are shown below:
MEASUREMENTS 1 MEASUREMENTS 2 MEASUREMENTS 3 MEASUREMENTS 4
IA Magnitude 0 A A Phase Watts 0 W IA Local 0 A Ch 1 Prop Delay
IA Phase Angle 0 deg B Phase Watts 0 W IA Angle Local 0 deg Ch 2 Prop Delay
IB Magnitude 0 A C Phase Watts 0 W IB Local 0 A Ch1 Rx Prop Delay
IB Phase Angle 0 deg A Phase VArs 0 Var IB Angle Local 0 deg Ch1 Tx Prop Delay
IC Magnitude 0 A B Phase VArs 0 Var IC Local 0 A Ch2 Rx Prop Delay
IC Phase Angle 0 deg C Phase VArs 0 Var IC Angle Local 0 deg Ch2 Tx Prop Delay
IN Derived Mag. 0 A A Phase VA 0 VA IA remote 1 0 A Channel 1 Status
IN Derived Angle 0 deg B Phase VA 0 VA IA Ang remote 1 0 deg Channel 2 Status
ISEF Magnitude 0 A C Phase VA 0 VA IB remote 1 0 A IM64 Rx Status
ISEF Angle 0 deg 3 Phase Watts 0 W IB Ang remote 1 0 deg STATISTICS
I1 Magnitude 0 A 3 Phase VArs 0 VAr IC remote 1 0 A Last Reset on
I2 Magnitude 0 A 3 Phase VA 0 VA IC Ang remote 1 0 deg Date/Time
I0 Magnitude 0 A 3Ph Power Factor 0 IA remote 2 0 A Ch1 No.Vald Mess
IA RMS 0 A APh Power Factor 0 IA Ang remote 2 0 deg Ch1 No.Err Mess
IB RMS 0 A BPh Power Factor 0 IB remote 2 0 A Ch1 No.Errored s
IC RMS 0 A CPh Power Factor 0 IB Ang remote 2 0 deg Ch1 No.Sev Err s
IN RMS 0 A 3Ph WHours Fwd 0 Wh IC remote 2 0 A Ch1 No.Dgraded m
VAB Magnitude 0 V 3Ph WHours Rev 0 Wh IC Ang remote 2 0 deg Ch2 No.Vald Mess
VAB Phase Angle 0 deg 3Ph VArHours Fwd 0 VArh IA Differential 0 A Ch2 No.Err Mess
VBC Magnitude 0 V 3Ph VArHours Rev 0 VArh IB Differential 0 A Ch2 No.Errored s
VBC Phase Angle 0 deg 3Ph W Fix Demand 0 W IC Differential 0 A Ch2 No.Sev Err s
VCA Magnitude 0 V 3Ph VArs Fix Dem. 0 VAr IA Bias 0 A Ch2 No.Dgraded m