EasyManua.ls Logo

Alstom MiCOM P545 - 3.2.6 Zone 1 phase and ground reach settings; 3.2.7 Zone 2 phase and ground reach settings; 3.2.8 Zone 3 phase and ground reach settings; 3.2.9 Zone 3 reverse reach

Alstom MiCOM P545
1024 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Application Notes P54x/EN AP/La4
MiCOM P543, P544, P545 & P546
(AP) 6-57
AP
3.2.6 Zone 1 phase and ground reach settings
Required Zone 1 reach is to be 80% of the line impedance between Green Valley and Blue
River substations.
Setting the Relay in the SIMPLE setting mode (recommended):
Set Zone 1 Ph and Zone 1 Gnd reach = 80%
From this the relay will automatically calculate the required ohmic reaches, or they can be
entered manually in the ADVANCED mode, as follows:
Required Zone 1 reach = 0.8 x 100 x 0.484 79.4 x 0.12
Z1 = 4.64 79.4 secondary
The Line Angle = 80
Therefore actual Zone 1 reach, Z1 = 4.64 80 secondary.
3.2.7 Zone 2 phase and ground reach settings
Req
uired Zone 2 impedance = (Green Valley-Blue River) line impedance + 50%
(Blue River-Rocky Bay) line impedance
Z2 = (100+30) x 0.484 79.4 x 0.12 = 7.56 79.4
secondary.
The Line Angle = 80
Actual Zone 2 reach setting = 7.56 80 secondary
Alternatively, in SIMPLE setting mode, this reach can be set as a percentage of the
protected line. Typically a figure of at least 120% is used.
3.2.8 Zone 3 phase and ground reach settings
Req
uired Zone 3 forward reach = (Green Valley-Blue River + Blue River-Rocky Bay) x
1.2
= (100+60) x 1.2 x 0.484 79.4 x 0.12
Z3 = 11.15 79.4 ohms secondary
Actual Zone 3 forward reach setting = 11.16 80 ohms secondary
Alternatively, in SIMPLE setting mode, this reach can be set as a percentage of the
protected line.
3.2.9 Zone 3 reverse reach
In
the absence of other special requirements, Zone 3 can be given a small reverse reach
setting, of Z3’ = 10%. This is acceptable because the protected line length is > 30km.
Zone 4 Reverse Settings with POR and BLOCKING schemes
Where zone 4 is used to provide reverse directional decisions for Blocking or Permissive
Overreach schemes, zone 4 must reach further behind the relay than zone 2 for the remote
relay. This can be achieved by setting: Z4 ((Remote zone 2 reach) x 120%), where mho
characteristics are used.

Table of Contents

Related product manuals