Settings P54x/EN ST/La4
MiCOM P543, P544, P545, P546
(ST) 4-91
ST
Setting range
Menu text Default setting
Min. Max.
Step size
SNTP PARAMETERS
SNTP Server 1 Data
Displays the IP address of the primary SNTP server.
SNTP Server 2 Data
Displays the IP address of the secondary SNTP server.
IEC61850 SCL
IED Name Data
8 character IED name, which is the unique name on the IEC 61850 network for the IED,
usually taken from the SCL file.
IEC61850 GOOSE
GoID Data
64 character GOOSE Identifier, used for naming the published GOOSE message. Default
GoID is TEMPLATESystem/LLN0$GO$gcbST.
GoEna Disabled Disabled, Enabled
Setting to enable GOOSE publisher settings.
Test Mode Disabled Disabled, Pass Through, Forced
The Test Mode cell allow the GOOSE message, for example
n
t
OOSE
the ‘V ting below. Once testing is complete the cell
s the test pattern to be sent in
for testing or commissioning. When ‘Disabled’ is selected, the test flag is not set. Whe
‘Pass Through’ is selected, the test flag is set, but the data in the GOOSE message is sen
as normal. When ‘Forced’ is selected, the test flag is set, and the data sent in the G
message is as per OP Test Pattern’ set
must be set back to ‘Disabled’ to restore the GOOSE scheme back to normal service.
VOP Test Pattern 0x00000000 0x00000000 0xFFFFFFFF 1
The 32 bit test pattern applied in ‘Forced’ test mode.
Ignore Test Flag No No, Yes
When set to ‘Yes’, the test flag in the subscribed GOOSE message is ignored, and the data
. treated as normal
1.4.15 C
Menu text Default setting Setting rang
ontrol input labels
e Step size
CTRL I/P LABELS
Control Input 1 Control Input 1 16 Character Text
Setting to change the text associated with each individual control input. This text will be
displayed when a control input is accessed by the hotkey menu, or it can be displayed i
n
able schemthe programm e logic.
Control Input 2 to 32
Control Input
2 to 32
16 Character Text
Setting to change the text associated with each individual control input. This text will be
displayed when a control input is accessed by the hotkey menu, or it can be displayed in
the programmable scheme logic.