P54x/EN PL/La4 Programmable Logic
(PL) 7-16
MiCOM P543, P544, P545 & P546
PL
1.7 Description of logic nodes
Note: Where applicable. Not all nodes appear in every product variant.
DDB no. English text Source Description
0 Output R1 Output Conditioner Assignment of signal to drive output Relay 1
31 Output R32 Output Conditioner Assignment of signal to drive output Relay 32
32 Input L1 Opto Input From opto input 1 - when opto energized
55 Input L16 Opto Input From opto input 24 - when opto energized
63 Input L24 Opto Input From opto input 32 - when opto energized
64 to 95 Not used
96 IM64 Ch1 Input 1 IM64
IM64 Ch1 input 1 - is driven by a message
from the remote line end
103 IM64 Ch1 Input 8 IM64
IM64 Ch1 input 8 - is driven by a message
from the remote line end
104 IM64 Ch2 Input 1 IM64
IM64 Ch2 input 1 - is driven by a message
from the remote line end
111 IM64 Ch2 Input 8 IM64
IM64 Ch2 input 8 - is driven by a message
from the remote line end
112 IM64 Ch1 Output 1 PSL
IM64 Ch1 output 1 - mapping what will be sent
to the remote line end
119 IM64 Ch1 Output 8 PSL
IM64 Ch1 output 8 - mapping what will be sent
to the remote line end
120 IM64 Ch2 Output 1 PSL
IM64 Ch2 output 1 - mapping what will be sent
to the remote line end
127 IM64 Ch2 Output 8 PSL
IM64 Ch2 output 8 - mapping what will be sent
to the remote line end
128 Relay Cond 1 PSL Input to relay 1 output conditioner
159 Relay Cond 32 PSL Input to relay 32 output conditioner
160 Timer in 1 PSL Input to auxiliary timer 1
175 Timer in 16 PSL Input to auxiliary timer 16
176 Timer out 1 Auxiliary Timer Output from auxiliary timer 1
191 Timer out 16 Auxiliary Timer Output from auxiliary timer 16
192 Control Input 1 Control Input Command
Control input 1 - for SCADA and menu
commands into PSL
223 Control Input 32 Control Input Command
Control input 32 - for SCADA and menu
commands into PSL
256 Virtual Output 1 PSL
Virtual output 1 - allows user to control a
binary signal which can be mapped via
SCADA protocol output to other devices
287 Virtual Output32 PSL
Virtual output 32 - allows user to control a
binary signal which can be mapped via
SCADA protocol output to other devices
288 SG-opto Invalid Group Selection
Setting group selection opto inputs have
detected an invalid (disabled) settings group
289 Prot'n Disabled Commissioning Test
Protection disabled - typically out of service
due to test mode
290 Static Test Mode Commissioning Test
Static test mode option bypasses the delta
phase selectors, power swing detection and
reverts to conventional directional line and
cross polarization to allow testing with test sets
that can not simulate a real fault
291 Test Loopback C Diff Loopback test in service (external or internal)
292 Test IM64 C Diff Indication that relay is in test mode