EasyManua.ls Logo

Alstom MiCOM P545 - 6.7 Worked example for CT requirements; 6.7.1 Important notes to be considered; 6.7.2 System data; 6.7.3 Calculation of Primary X;R

Alstom MiCOM P545
1024 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Application Notes P54x/EN AP/La4
MiCOM P543, P544, P545 & P546
(AP) 6-85
AP
6.7 Worked example for CT requirements
The Power system and the line parameters (Line length: 100 km) as given in section 3.2 is
use
d here to calculate CT requirements.
6.7.1 Important notes to be considered
Current differential – Both If and X/R are to be calculated for a through fault
Distance Zone1 reach point case – Both If and X/R are to be calculated for a fault at
Zone1 reach point
For calculating the CT requirements, the bus bar short time symmetrical fault rating shall
be considered as the bus fault level.
When there are only indicative X/Rs available, then the circuit breaker’s dc breaking
capacity shall be used to arrive at the primary time constant (and hence the primary
system X/R). The derivation shall be obtained from the circuit breaker manufacturer;
practical primary time constants arrived in such a way vary between 50 ms (applicable
for 66 kV and 132 kV breakers) and 120 ms (applicable for 220 kV and 400 kV
breakers). 150 ms is a practical figure for generator circuit breakers.
6.7.2 System data
In the following exampl
e, the following parameters have been considered for the CT
calculations:
System voltage - 230 kV
System frequency - 50 Hz
System grounding - solid
Single circuit operation between Green Valley and Blue River
CT ratio - 1200/1
Line length - 100 kms
Line positive sequence impedance Z1 = 0.089 + j 0.476 ohm / km
Bus fault level - 40 kA
Primary time constant = 120 ms
6.7.3 Calculation of Primary X/R
Primary X/R till the Green
Valley bus = 2 * pi * f * primary time constant in s
= 2 * pi * 50 * 0.12
Primary X/R till the bus = 37.7
6.7.4 Calculation of Source Impedance Zs
Source Impe
dance Zs = 230 kV / (1.732 * 40 kA)
= 3.32 ohms
Source angle = tan-1 (X/R)
= tan-1 (37.7)
= 88.48 deg
Hence, Zs = 0.088 + j 3.317 ohms

Table of Contents

Related product manuals