P54x/EN OP/La4 Operation
(OP) 5-206
MiCOM P543, P544, P545 & P546
OP
Live Line and Live Bus 2 signals are both set;
AND
None of the selected CB2 CS1 Volt. Blk conditions (V<, V>, VDiff) are true;
AND
If CB2 CS2 SlipCtrl setting is Enabled, the measured slip frequency between the line
VT and Bus1 VTs is less than the CB2 CS2 SlipFreqsetting;
AND
The measured phase angle magnitude is decreasing;
AND
If the CB2 CS2 Adaptive setting is Disabled, the measured phase angle magnitude is
less than the CB2 CS2 Angle setting;
OR
If the CB2 CS2 Adaptive setting is Enabled, AND if the predicted phase angle when
CB2 closes (after CB2 Cl Time setting) is less than the CB2 CS2 Angle setting AND as
close as possible to zero AND still decreasing in magnitude.