AMETEK CTs NetWave
8.5.6. Fuses NetWave 108.x
The fuses are located at the rear side of the NetWave behind the cover. For replace the user must open the
screws at the cover.
F1…F3 Fuses for General Input Line R, S, T
Rated voltage: 500 V
Rated current : 315 A
Type : NH2 gL / gG ITALWEBER 162031
Breaking capacity: >100 kA
F4 – F 12 Fuses for Line Inverter phase unit R, S, T
Rated voltage: 400 V
Rated current : 125 A slow blow
Dimension : 14 x51 mm
Type : SCH14 gG ITALWEBER 1431100
Breaking capacity: >120 kA
F13 – F 21 Fuses for Charge resistor
Rated voltage: 500 V
Rated current : 1 A slow blow
Dimension : 10 x 38 mm
Type : aM Legrand
Breaking capacity: >100 kA
F22, F 23 Fuses for Input Auxiliary Transformer
Rated voltage: 500 V
Rated current : 8 A slow blow
Dimension : 10 x 38 mm
Type : aM Wimex
Breaking capacity: >120 kA
F24, F 25 Fuses for Output Auxiliary Transformer
Rated voltage: 250 V
Rated current : WGT 15 A slow blow
Dimension : 5 x 20 mm
F26 - F 28, Fuses for Controller
F32, F36
Rated voltage: 250 V
Rated current : WGT 6.3 A slow blow
Dimension : 5 x 20 mm
F29 – F 31, Fuses for Aux. Supply Inverter Phase R, S, T and Fan
F33 – 35, F37-F39
Rated voltage: 250 V
Rated current : WGT 2.5 A slow blow
Dimension : 5 x 20 mm
F40, F41 Fuses for Safety Circuit
Rated voltage: 250 V
Rated current : WGT 1 A slow blow
Dimension : 5 x 20 mm