34
B00-1 Max./base
frequency simple
setting
(V/f control)
1 0 9 Select the output frequency rating from the combination
below.
B00-2
Motor rated output
(V/f control)
Inverte
r rating
(kW)
0.10 750.00 The motor rated output at the base frequency is set.
B00-3 Motor rated output
(V/f control)
Vac 230.
or
400.
(V)
39 480 This is the Motor rated Voltage. Set the voltage
mentioned on the motor nameplate. The setting value
depends on the 400V, 500V or 600V Series model.
B00-4
Max. frequency
(Fmax)
(V/f control)
50.00
(Hz)
Fbas
e or
3.00
Fbase
*7 or
440.0
0
When "B00-1" is a value other than 0, this will be
rewritten with the data set in the simple setting.
B00-5 Base frequency
(Fbase)
(V/f control)
50.00
(Hz)
Fmax/
7 or
1.00
Fmax
or
440.00
B00-6
Motor rated
current
(V/f control)
Invert
er
rating
(A)
Invert
er
rating
× 0.3
Inverte
r rating
This is the reference value for the over current limit,
OLT, current % display, analog input and output.
B17-0
V/f middle point
Setting-Freq 1
0.00 0.00
Max
freque
ncy
= 5Hz, frequency
B17-1
V/f middle point
Setting-Volt 1
0.0% 0.0 200 = 18%, voltage
B17-2
V/f middle point
Setting-Freq 2
0.00 0.00
Max
freque
ncy
= 8Hz, frequency
B17-3
V/f middle point
Setting-Volt 2
0.0% 0.0 200 = 26%, voltage
B17-4
V/f middle point
Setting-Freq 3
0.00 0.00
Max
freque
ncy
= 10Hz, frequency
B17-5 V/f middle point
Setting-Volt 3
0.0% 0.0 200 = 28%, voltage
B17-B
V/f middle point
use selection
1 2 1 = 2, function valid
C03-d
AFS1, Speed
setting 1
16 -11 16 = 0
C04-0
PROG 0 -11 16 =16 Multi speed function is valid
C04-2
S0, Prog. speed
selection
0 -11 16 = Select PSI for first speed
C04-3
S1, Prog. speed
selection
0 -11 16 = Select PSI for second speed
C04-4
S2, Prog. speed
selection
0 -11 16 = Select PSI for second speed
Value Ftrq [Hz] Fmax [Hz]
0
Free setting on B00-4 and
B00-5
1 50 50
2 60 60
3
50
60
4
50
75
Value Ftrq [Hz] Fmax [Hz]
5 50 100
6
60
70
7
60
80
8
60
90
9
60
120