10 IQ-636X-2/E Installation Manual — P/N 52839:K3 9/28/15
Section 2: System Overview
2.1 System Description
The IQ-636X-2/E control panel is a modular, intelligent fire alarm control panel (FACP) with an
extensive list of powerful features. The control panel uses the CPS-24/E integral power supply with
battery charger. This is combined with a mounting chassis and cabinet to create a complete fire
alarm control system. The panel supports FlashScan® protocol. A single SLC loop is supported
with the basic equipment package; a second SLC loop can be added by attaching an optional loop
expander module (LEM-320).
Modular devices mount to the chassis to provide additional output circuits. Five cabinet options are
available for enclosing system components; each is available in red or black.
The control panel has the capacity for installing up to 636 addressable points; 159 detectors and
159 monitor/control modules per SLC (Signaling Line Circuit).
2.1.1 Standard Features
• Uses the VIEW® early warning fire detection and the FlashScan or Classic Loop Interface
Protocol (CLIP) families of detectors and modules
• Integral power supply with battery charger
• Four standard Notification Appliance Circuits (NAC), Class A or B
• Alarm, Trouble, Supervisory and Security relays
• Support for 32 annunciator addresses, with 10 special annunciator groups
• Supports Style 4, Style 6, Style 7 SLC loops
• Connections to easily mount an expander board to add a second SLC loop
• Releasing service using on-board NACs or FCM-1 modules
• Logic Equations
• Display scroll selection
• Alarm verification supervisory indication (NYC)
• Supervisory duct detectors
• Supports Advanced Warning Addressable Combustion Sensing (AWACS) algorithms
• Battery charger supports 18 to 200 amp hour sealed lead-acid batteries
• EIA-485 connections for wiring ACS annunciators (including LDM custom graphic
annunciators), TM-4 transmitter
• EIA-232 connections for printer, CRT or printer/CRT
• Autoprogram feature for faster programming of new devices
• The control panel provides 6 amps of usable output power in an alarm condition; it provides
3 amps of usable output power in normal or continuous operating conditions
• Diagnostic LEDs and switches
• Ground fault detection (0 ohm impedance)
• Battery and battery-charger supervision, voltage-monitoring, and current-monitoring
• Disconnect of deeply-discharged battery (low battery disconnect)
• Programmable for strobe synchronization
• Mass Notification System compatible