54 IQ-636X-2/E Installation Manual — P/N 52853:K3 9/28/15
Applications Releasing Applications
d) Maintain a 0.25 inch (6.35 mm) spacing between the non-power-limited releasing circuit
device wiring and any power-limited circuit wiring.
!
WARNING:
The XP6-C is not listed for releasing applications and cannot be substituted for FCM-1
NOTE: As per UL 864 9th Edition, a supervisory signal must be indicated at the panel whenever
a releasing circuit is physically disconnected. Use a monitor module to monitor dry contacts off the
switch. See 4.11.