3. Operation of the Control Panel Normal Mode of Operation
22 IQ-636X Operations Manual P/N 52181:A 04/28/2005
Normal Mode of Operation
The system operates in Normal mode when no alarms or troubles exist. In Normal mode, the control
panel displays a System Normal message as follows
Figure 5 Sample System Normal Message
In Normal mode, the control panel does the following functions at regular intervals:
Polls all SLC devices, Panel Circuits, and the four NACs to check for valid replies, alarms,
troubles, circuit integrity, and supervisory signals, and so forth
Checks power supply troubles and batteries at 10-second intervals
Sends a supervisory query on the optional terminal mode LCD-80 and verifies proper response
Refreshes the LCD display and the optional terminal mode LCD-80 display and updates time
Scans for any keypad or Control Key entries
Performs a detector automatic test operation
Tests system memory
Monitors for microcontroller failure
SYSTEM NORMAL 01:56P 071401 Sat

Table of Contents