EasyManua.ls Logo

Ansul AUTOPULSE IQ-636X - Waterflow Circuit Operation; Style 6 and Style 7 Operation

Ansul AUTOPULSE IQ-636X
84 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Waterflow Circuit Operation 3. Operation of the Control Panel
IQ-636X Operations Manual P/N 52181:A 04/28/2005 39
Silence Inhibit Timer
A timer that disables the
SIGNAL SILENCE key function for the programmed time (0-300 seconds) when
a fire alarm occurs. A Silence Inhibit Timer starts at the first fire alarm and restarts with each new fire
alarm.
Waterflow Circuit Operation
If a monitor module programmed with a WATERFLOW Type Code initiates a fire alarm, the control panel
disables the
SIGNAL SILENCE key and the Auto Silence Timer. Refer to the IQ-636X Installation Manual
for information on Waterflow circuits.
Style 6 and Style 7 Operation
Style 6 and Style 7 are supervised methods of communicating with addressable devices. If the control
panel detects a trouble (open or short), it will drive both ends of the loop, maintaining communication in
an unsupervised method. The latching trouble will display on the panel as a Style 6 trouble until you
correct the condition and press reset. Style 7 configuration of the SLC requires the use of ISO-X
modules.

Table of Contents

Related product manuals