Output Circuit Trouble Mode of Operation 3. Operation of the Control Panel
IQ-636X Operations Manual P/N 52181:A 04/28/2005 35
Output Circuit Trouble Mode of Operation
Overview
Output circuits include NACs, Panel Circuits 1-64, Control/Relay Modules, and Transponder Points.
This section contains a description of control panel operation for each type of output circuit.
Four NACs are included on the control panel
Panel Circuits include ICM-4RK or CRM-4RK panel modules via connection to the control
panel
Control/Relay Modules connected to the control panel on an SLC
Transponder Points include XP5-C or XP6-C (CLIP or FlashScan).
Table 9 Control Module and Panel/NAC Circuit Trouble Type Codes
Trouble Type Codes for Control Modules and Panel/NAC Circuits
Type Code
Silenceable
(Y/N)
Configuration Device Function
CONTROL N Panel Circuit relay or NAC Supervised NAC
RELAY N FORM-C relay Relay Output
BELL CIRCUIT N Panel Circuit relay or NAC Supervised NAC for notification appliance
STROBE CKT N Panel Circuit relay or NAC Supervised NAC for notification appliance
HORN CIRCUIT N Panel Circuit relay or NAC Supervised NAC for notification appliance
AUDIBLE CKT N Panel Circuit relay or NAC Supervised NAC for notification appliance
SPEAKER N Panel Circuit relay or NAC Supervised NAC for speaker circuit
REL END BELL N Panel Circuit relay or NAC Supervised NAC for notification appliance
blank N Panel Circuit relay or NAC Supervised NAC for undefined device
RELEASE CKT N NAC Directs outputs to perform a releasing function.
REL CKT ULC N NAC Directs outputs to perform a release function as required by ULC.
REL AUDIBLE N Panel Circuit Relay or NAC NAC, activated upon release
NONRESET CTL* N Form-C Relay and NAC Relay output, unaffected by “System Reset” command
TELEPHONE N Panel Circuit relay or NAC Standard Telephone circuit
REL CODE BELL** N NAC only Supervised NAC (IQ-636X NAC only)
INSTANT RELE N NAC NAC, short = normal; supervised for open circuits and ground faults.
Always non-silenceable and switch-inhibited.
ALARMS PEND N Panel Circuit or NAC Output that will activate upon receipt of an alarm condition, and remain
in the alarm state until all alarms have been acknowledged.
CONTROL NAC** N Panel Circuit relay or NAC Supervised NAC
GEN ALARM Y Control Module, XP6-C, or an XP5-C (in NAC mode) configured as a
Municipal Box Transmitter for NFPA 72 Auxiliary Fire Alarm Systems
application. This Type ID can also be used for general alarm activation.
GEN SUPERVIS Y Control Module, XP6-R, or an XP5-C (in relay mode) activated under
any Supervisory condition (includes sprinkler type).
GEN TROUBLE Y Control Module, XP6-C, or an XP5-C (in relay mode) activated under
any System Trouble condition.
GENERAL PEND Y Control Module, XP6-C, or an XP5-C (in NAC mode) that will activate
upon receipt of an alarm and/or trouble condition, and remain in the ON
state until all events have been ACKNOWLEDGED.
TROUBLE PEND N Control Module, XP6-C, or an XP5-C (in NAC mode) that will activate
upon receipt of a trouble condition, and remain in the ON state until all
troubles have been ACKNOWLEDGED.
* Type Code is Control Module type code only.
** Type Code is Panel/NAC Circuit type code only.