Using the CRT-2 for Alter Status Appendix C: Remote Terminal Access
IQ-636X Operations Manual P/N 52181:A 04/28/2005 75
Using the CRT-2 for Alter Status
Overview
This section shows how to do Alter Status functions from a CRT-2
Note: The panel must be in Local Terminal Mode (LocT) or Local Monitor Mode (LocM).
Note: See the IQ-636X Programming Manual for instructions on enabling the CRT port.
Table 23 Alter Status Functions
Accessing Alter Status Options
Access the Alter Status function from the CRT-2 by following these steps.
1. Turn on the CRT-2 connected to the control panel.
2. Press the Alter Status function key. The control panel displays the Password screen:
3. Enter the Status Change Password. The factory default Status Change Password is 11111. The
password does not display on the CRT-2. Five asterisks will appear in place of the password:
The Alter Status Options menu appears:
From the Alter Status Options menu, you can select options 1-5.
Function Lets you...
Disable Enable or disable detectors, modules, or panel circuits.
Alarm/Pre-Alarm Change the Alarm and Pre-Alarm levels of any addressable detector in
the system.
Clear Verification Clear the verification counter for all the addressable detectors in the
system.
Clear History Clear the contents of the History buffer.
Set Action/Alert Set the Pre-Alarm for Alert or Action.
Enter Status Change Password or Escape to Abort
C
Press
*****
11111W
Press
1=Disable 2=Alarm/Prealarm 3=Clear Verification 4=Clear History 5=Alert/Action