Description
The Selector Valve Pneumatic Actuation Line Kit (Part No.
436127) is used to control the pressure in the actuation
lines of the selector valves. One selector valve pneumatic
actuation line kit is required for each Pneumatic Actuator
(Part No. 428566) and must be installed within 1 ft (0.3 m)
of the actuator/isolation valve.
The Low Pressure Vent Plug (Part No. 436085) and Safety
Relief Valve (Part No. 15677) are to be installed with a
torque of 125 in.-lb (14 N m).
After system discharge, all pressure in the actuation line
must be relieved by pulling the ring on the safety relief
valve.
System Components
UL EX-4510 2-1-12 Page 1-3.8
Selector Valve Pneumatic Actuation Line Kit
008246
ANSUL
®
Copyright © 2012 Tyco Fire Products LP.
All rights reserved.
Form No. F-2012053
One Stanton Street +1-715-735-7411
Marinette, WI 54143-2542 www.ansul.com
Shipping Assembly
Part No. Description
436127 Selector Valve Pneumatic
Actuation Line Kit
436085 Low Pressure Vent Plug
15677 Safety Relief Valve
28484 1/4 in. Close Nipple
27350 1/4 in. Tee
Component Material Approvals
Low-Pressure Brass UL Listed (EX-4510);
Vent Plug Listed for use with
FM Approved systems
Safety Relief Brass UL Listed (EX-4510);
Valve Listed for use with
FM Approved systems
1/4 in. Close Galvanized UL Listed (EX-4510);
Nipple Steel Listed for use with
FM Approved systems
1/4 in. Tee Galvanized UL Listed (EX-4510);
Steel Listed for use with
FM Approved systems
Note: The low pressure vent plug cannot be ordered sepa-
rately.
4 3/4 IN.
(121 mm)
1 3/4 IN.
(44 mm)
1/4 IN.
TEE
1/4 IN.
CLOSE
NIPPLE
LOW PRESSURE
VENT PLUG
SAFETY
RELIEF
VALVE