System Components
UL EX-4510 2-1-12 Page 1-16.2
REV. 2
Description
The INERGEN
® system nozzle deflector shield is used to
control the pattern of the discharge of the INERGEN agent.
The deflector shield helps keep the agent discharge away
from false ceiling tiles and fragile light fixtures, avoiding
damage to them.
The deflector shields are constructed of steel and painted
with a cameo cream colored paint. They are available in
five sizes.
Nozzle Deflector Shield
Component Material Approvals
Nozzle Steel UL Listed (EX-4510);
Deflector Listed for use with
Shield FM Approved systems
Shipping A B C D E
Assembly Inlet Length of Overall Deflector Coupling
Part No. NPT Coupling Length O.D. O.D.
417708 1/2 in. 1 7/8 in. 3 in. 3 3/8 in. 1 1/8 in.
(4.8 cm) (7.6 cm) (8.6 cm) (2.9 cm)
417711 3/4 in. 2 in. 3 1/4 in. 3 3/8 in. 1 3/8 in.
(5.1 cm) (8.3 cm) (8.6 cm) (3.5 cm)
417714 1 in. 2 3/8 in. 3 13/16 in. 4 7/8 in. 1 3/4 in.
(6.0 cm) (9.7 cm) (12.4 cm) (4.4 cm)
417717 1 1/4 in. 2 5/8 in. 4 3/16 in. 4 7/8 in. 2 1/4 in.
(6.7 cm) (10.6 cm) (12.4 cm) (5.7 cm)
417720 1 1/2 in. 3 1/8 in. 4 29/32 in. 5 21/32 in. 2 1/2 in.
(7.9 cm) (12.5 cm) (14.4 cm) (6.4 cm)
D
B
A
C
E
003651
NOTE: There are no deflector shields available for the 2, 2 1/2, or 3 in. models.