56
TC5-2V2SA.rev.05
FACTORY SETTINGS
PARAMETER
FACTORY
SETTING
RANGE OF
VALUES
Temperature Set Point 75
o
F(23.9
o
C)
-40 to 99.9
o
F
(-40 to 37.7
o
C)
Stage 1
Minimum
Speed
40 % 10 % to 100 %
Time On 15 seconds
0 to 900 seconds by
increments of 15
seconds
Time Off 0 seconds
Bandwidth 2
o
F(1.1
o
C)
0.5 to 20
o
F
(0.3 to 11.1
o
C)
Humidity
Control
Humidity Set
Point
65%
40 to 100%
relative humidity
Compensation
Percentage
60%
0 to 100% of stage 1
minimum speed
Stage 2
Offset 0.5
o
F (0.3
o
C)
0 to 20
o
F
(0 to 11.1
o
C)
Bandwidth 2
o
F(1.1
o
C)
0.5 to 20
o
F
(0.3 to 11.1
o
C)
Min. Speed 40 % 10 % to 100 %
De-icing
Cycle Time
1 minute
1 to 720 minutes, by
increments of 1
minute
De-icing
Time
0 seconds
0 to 900 seconds, by
increments of 1
second
Stages
3 and 4
Differential 2
o
F(1.1
o
C)
0.5 to 20
o
F
(0.3 to 11.1
o
C)