User Manual Smart-UPS RC XLI/XLICH/XLI-CC 1000/2000/3000 VA 220/230/240 Vac Tower/Rack-Mount 4U 4
Specifications
Environmental Specifications
Physical Specifications
Temperature
Operating 0° to 40° C (32° to 104° F)
This unit is intended for indoor use
only. Select a location sturdy enough to
handle the weight.
Do not operate UPS where there is
excessive dust or temperature or
humidity are outside specified limits.
Be sure air vents on UPS are not
blocked. Allow adequate space for
proper ventilation.
Environmental factors impact battery
life. High temperatures, poor utility
power, and frequent, short duration
discharges will shorten battery life.
Storage -15° to 45° C (5° to 113° F)
charge UPS battery every six months
Maximum
Elevation
Operating 3,000 m (10,000 ft)
Storage 15,000 m (50,000 ft)
Humidity
0 to 95% relative humidity, non-condensing
Weight - Refer to Safety Guide supplied with this unit for lifting guidelines.
UPS 1000/2000 VA 3000 VA
UPS with batteries 26 kg (57 lbs) 34 kg (75 lbs)
UPS without batteries 13 kg (29 lbs) 14 kg (31 lbs)
Each battery module 13 kg (29 lbs) 10 kg (22 lbs)
1000/2000 VA models: The 96 V battery string is a single module.
3000 VA models: The 96 V battery string consists of two 48 V battery modules.
Maximum number of XLBPs supported by Smart-UPS RC
10
Combined weights of UPS and all
XLBPs installed in a rack must not
exceed rack weight limits.
Dimensions
Length x Width x Height:
46 cm (18 in) x 43 cm (17 in) x 18 cm (7 in)