Smart-UPS SRC 5000/6000/8000/10000 VA4
Rear panel
Specifications
Feature Description
Serial Com Power management software and interface kits can be used with the UPS.
Use only interface kits supplied or approved by APC.
Parallel port Serial ports for communication between two UPS units configured in
parallel.
EPO terminal block The optional Emergency Power Off (EPO) feature allows connected loads to
be immediately de-energized from a remote location, without switching to
battery operation see “Emergency Power Off” section.
External battery pack connectors Optional external battery packs provide extended runtime during power
outages. These units support up to 9 external battery packs. Refer to the APC
Web site www.apc.com, for information on external battery packs.
5000/6000 VA models: SRC192XLBP
8000 VA models: SRC240XLBP1
10000 VA models: SRC240XLBP2
Input circuit breaker The input circuit breaker must be switched on for the UPS to operate.
The input circuit breaker protects the UPS from extreme overload conditions.
Temperature
Operating
0° to 40° C (32° to 104° F)
This unit is intended for indoor use only.
Select a location sturdy enough to handle
the weight.
Do not operate UPS where there is
excessive dust or temperature or humidity
are outside specified limits.
This unit has air vents. Allow adequate
space for proper ventilation.
Environmental factors impact battery life.
High temperatures, poor utility power, and
frequent, short duration discharges will
shorten battery life.
Storage
-15° to 45° C (5° to 113° F)
charge UPS battery every six months
Maximum
Elevation
Operating
2,000 m (6,500 ft)
Storage
15,000 m (50,000 ft)
Humidity
0% to 95% relative humidity, non-condensing
oem0075a