MEAS:FREQ:MOD:CHAN {<mode>}
Setting of channel of frequency measurement. Parameter is 0 (auto), 1 6 (channel).
MEAS:ENER:STAR
Start of energy accumulation (if stopped).
MEAS:ENER:STOP
Stop of energy accumulation (if started).
MEAS:ENER:RES
Reset (clearing to zero) of energy accumulation values.
MEAS:ENER:STAT?
Request for status of energy accumulation. Answer is 0 (stopped) or 1 (started).
MEAS:ENER:ACT?
Request for active energy values in Ws.
MEAS:ENER:ACT:PRIM?
Request for primary active energy values in Ws.
MEAS:ENER:ACT:K?
Request for active energy values in kWh.
MEAS:ENER:ACT:PRIM:K?
Request for primary active energy values in kWh.
MEAS:ENER:ACT:CHAN? {<channel (0|1|2)>}
Request for active energy values in Ws in particular channel. Parameter channel can be 0=L1, 1=L2,
2=L3.
MEAS:ENER:ACT:CHAN:PRIM? {<channel (0|1|2)>}
Request for primary active energy values in Ws in particular channel. Parameter channel can be 0=L1,
1=L2, 2=L3.
MEAS:ENER:ACT:CHAN:K? {<channel (0|1|2)>}
Request for active energy values in kWh in particular channel. Parameter channel can be 0=L1, 1=L2,
2=L3.
MEAS:ENER:ACT:CHAN:PRIM:K? {<channel (0|1|2)>}
Request for primary active energy values in kWh in particular channel. Parameter channel can be 0=L1,
1=L2, 2=L3.
MEAS:ENER:REAC?
Request for reactive energy values in vars.
MEAS:ENER:REAC:PRIM?
Request for primary reactive energy values in vars.
MEAS:ENER:REAC:K?
Request for reactive energy values in kvarh.
MEAS:ENER:REAC:PRIM:K?
Request for primary reactive energy values in kvarh.