CS175-275-575-875 Installation Guide
12 PROGRAMMING THE PANEL
12.1 Default programming
For most routine installations, the default programming allows a majority of the locations
available with the CSx75 to be enabled, when communicating in Contact ID or SIA
formats and without partitioning.
12.2 Entering programming mode
1. Press
8
.
2. Enter a Go to program code.
3. You are now in programming mode and ready to select the module to program.
4. Enter the module number and press #.
12.3 Selecting a module to program
Since all modules connected to the CSx75 are programmed through the keypad, the
module you are programming should be the first entry.
To program a module, enter the module number and press #. Not all of these modules
may yet be available.
0
Control panel
16-23
Hardware expanders
24-31
Relay/voltage output modules
32-36
RF Receiver modules
64-68
Verification modules
GSM
GSM modules
12.4 Loading factory defaults for the controller
1. Enter programming mode as described in
Entering programming mode
.
2. Press
0#
for the controller.
3. Press 910# as the reset command.
4. The keypad beeps three times to indicate that loading is in progress. This takes
about six seconds.
"
Other modules, such as keypads, RF receiver modules and output expanders, can be
reset in the same way. See Appendix 3 for a list of keypad module numbers.