10
Armstrong International
Parc Industriel Des Hants-Sarts, 2ème Avenue No. 4, Haerstal, B-4040, Belgium
armstronginternational.com/brain
General
Installation
Notes:
1. DRV80 is supplied fully performance and pressure tested.
2. The DRV80 must be installed in an area where it is accessible to do any maintenance tasks e.g. connecting
Laptop / PC, removal of the cover, replacing worn parts etc.
3. Suitable connections for ease of maintenance should be used on the inlet and outlet ports. (Isolation valves
and unions.)
4. The hot and cold water inlet supply pressures must be nominally equal.
5. The cold inlet supply feed to the DRV80 must be “tapped” directly from the cold inlet supply to the water heater.
6. The inlet supply pipework must be thoroughly flushed before fitting the DRV80.
200 mm
50 mm
100 mm 100 mm
150 mm
50 mm
The Brain
®
DRV80 MUST ONLY
be installed in this orientation.
These clearance dimensions are
recommended for maintenance
purposes.
Installation must be carried out in accordance with these instructions, and must be conducted by
designated, qualified and competent personnel.
The installation must comply with all relevant national and local water plumbing regulations.
The installation must comply with all relevant national and local electrical wiring regulations.
The DRV80 must be installed per the piping diagrams (pages 12 - 15). All plumbing components are to be
supplied by the installer. Failure to include these components will compromise the DRV and system performance.
Caution! The DRV80 must be installed in a dry area where it will not be able to freeze
(minimum ambient temperature of 2 °C).
Warning! The DRV80 must be EARTHED.
The DRV80 is intended to be permanently connected to the fixed electrical wiring.
A means for electrical isolation of the DRV80 shall be provided, this device must
be suitably located, easily reached and identified as to its purpose.