Appendices
62
Edit
Settings
Menu
Group
Submenu
items
Description
Type
Range
Default
Value
I channel 3
Edit/
Display
0.1-
999999
1.0
Alarm
Thresholds
Current
balance
%
Maximum permitted
current imbalance
Edit/
Display
0 100
60
Voltage
balance %
Maximum permitted
voltage imbalance
Edit/
Display
0 100
50
Voltage range
%
Maximum permitted
voltage upper limit
(as % above nominal)
Edit/
Display
0 100
90
Max
Current%
Maximum permitted
current upper limit
(as % above nominal)
Edit/
Display
0 100
90
Low voltage %
Minimum acceptable
level below which
voltage is considered
to be zero for line
and power fault
alarms (as % of
nominal)
Edit/
Display
0 100
20
Low current
Minimum acceptable
level below which
current is considered
to be zero for motor
not running alarm (as
% of nominal)
Edit/
Display
0-100 %
20
Current
Instability
Threshold for current
variation during data
acquisition. If the
current variation
exceeds this value,
the line is considered
to be unstable
Edit/
Display
0-100 %
45