ASCO Series 300 Quick Connect Power Panel
381333-476 www.ascopower.com
11
Set-up – Continued
4.
Disconnect the Ground (green) connections,
beginning
with the closest to the front door
Proper disconnection (See Figure 12):
A.
Grasp connector jacket firmly and rotate cam
connector clockwise until it stops
B.
Firmly pull on connector until it separates from the plug
C.
Set aside
5.
Continue with ALL Ground (green)
connections,
beginning with the front of the
cabinet and working
rearward
6.
Complete disconnect of ALL Neutral connections prior
to
proceeding
Step 10: Secure front door to complete.
Appendix A
Pre-Operation Checklist
1.
Visual inspection of enclosure
–
Ensure the ASCO Series 300 Quick Connect Power Panel
is firmly secured to its
base and/or building
–
Review conduit connection for signs of leakage
–
Ensure paint is intact with no signs of rust or corrosion
2.
Open main chamber door and remove rear and side
panels
–
Ensure unit is dry and free of debris
–
Ensure that gaskets are pliable and no cracking exists
–
Ensure that door hinges are secure and lubricated
–
Ensure that keylocks are intact and operational
–
Ensure that all load terminals are securely fastened and
that the
bolts are set at ninety-eight (98) foot pounds of
torque
–
Ensure paint is intact with no signs of rusting or corrosion
–
Ensure electrical connections are intact with no signs of
corrosion or cracking
3.
Review all safety labels and ensure that they are
present
and legible
–
Replace as needed
4.
Inspect all portable cables
–
Do not use cables if they appear frayed
–
Do not use cable if connectors or plug do not seat properly
–
Do not use cables if any copper wiring is exposed
5.
ASCO Power Services are available to assist in resolving
issues. If you have any questions or need technical advice
or
suggestions regarding this product, please contact
ASCO Power Technologies
at
1-800-800-2726(ASCO) or e-mail
powerwarranty@ascopower.com