Calor EVO HEAT PUMP
19
Water Pump
F40 Water Pump Select
0 – 1
1 -
0: water pump is not enable
1: water pump is enable
F41
Water pump starts time
before compressor starts
1 – 10
3 min
F42
Water pump stops time
after compressor stops
0 – 10
3 min
F43 Water pump stop time
1 – 99
60 min
F44 Water pump run time
OFF
1 – 10
5 min
Alarm
F50 External alarm mode 3 3 - 3: always closed, unlocked
F51 External alarm mode 3 3 - 3: always closed, unlocked
F52 External alarm mode 3 3 - 3: always closed, unlocked
F59
Buzzer alarm sound
duration
On: Alarm sound is always
on until pressing any key
RTC
F60 Set the RTC time 00:00—23:59 - -
OFF
05:00
-
OFF means not using
F62 Period 1 end time
07:00
-
F63 Period 2 start time
00:00—23:59
16:00
-
F64 Period 2 end time
18:00
-
F65 Period 3 start time
22:00
-
F66 Period 3 end time
OFF
00:00
-
F69 Run Mode 0/1 0 -
0:Automatic
1:Economical
F80 Password
OFF
0001 -- 9999
OFF -
System
setting
F81 Temperature unit C/F C -
C:
Centigrade
F: Fahrenheit
F85
Display accumulative
running time
Accumulative running
time reset
- - -
F87 Probation time
OFF
1 -- 9999
OFF hour
The controller will stop if the
accumulative time is over
probation time, and show the
alarm code “A99”.
OFF means no probation
Testing
F99 Test self
This function can attract all relays in turn, and please don’t use it
when the controller is running!