EasyManua.ls Logo

Astralpool ELITE 60 - Electrolysis Cell Installation

Astralpool ELITE 60
39 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
S I G N A T U R E
15
7.6.1. ELECTROLYSIS CELL INSTALLATION
The electrolysis cell is made of a transparent polymer in whose interior the electrodes are
placed. The electrolysis cell must be always installed indoors and after the pool lter, and
after any other equipment (heat pumps, control systems, etc.). The installation of the cell should
allow easy access to the installed electrodes by the user. It is highly recommended to install the
electrolysis cell VERTICALLY, in a place of the pipe that can be easily isolated from the rest of
the installation by two valves, so that the tasks of maintenance can be carried out with no need
of partial or total draining of the swimming pool.
Where the cell is installed on a by-pass (recommended option), a valve to regulate the ow must
be introduced. Previously to installation, please consider the following commentaries:
Flow direction marked in the cell must be respected.
Recirculation system must guarantee the minimum ow
stated in the Table of Technical Specications (see section 8
from the Operation Manual).
The system ow detector activates if there is not recirculation
(ow) of water through the cell or if ow is very low. If
electrolysis gases are not properly removed through the
electrolysis cell, the generated gas bubble electrically
isolates the auxiliary electrode (electronic detection).
Therefore, when locating the electrodes in the cell, the level
sensor (auxiliary electrode) will have to be located in the
higher area of the cell. The safest orientation is shown in the
recommended installation diagram.
WARNING: if the in-out valves of the electrolysis cell are
closed simultaneously, the ow detector (gas detector)
will not work correctly, with the consequent risk of cell
breakdown. Although this situation is extremely unusual,
since the Astralpool Chlore Elite System has an additional
external ow detector (ow switch), it can be easily avoided
once the equipment has been installed, by locking at opened
position the return valve to the swimming pool, so it cannot
accidentally be manipulated.
FlowFlow
FLOW
DETECTOR
(GAS)
CRITICAL
WATER LEVEL
GAS
WATER
FLOW
DETECTOR
(GAS)
CRITICAL
WATER LEVEL
GAS
WATER
1
2
3

Related product manuals