Figure 26 Distances from Openings into the Building
Figure 27 Permanently Fixing Window within Exclusion Zone
5.3.1 Window within Gas Meter Box Exclusion Zone
Windows within the exclusion zone must be permanently xed so they cannot open. Refer to
Figure 27. Permissible compliance methods are as follows:
Reversing the openable portion of the window
Permanently securing the window in the closed position with a minimum of two (2) rivets
or non-retractable screws in three (3) sides of the openable window portion. There must be
a minimum quantity of six (6) permanent xtures.
Note: A signed approval must be granted by AGA before proceeding with any gas meter
positions within 750mm of altered building windows or openings. Approval of
acceptable window xing is at the discretion of AGA.
28