3.1.2 Multi-Unit Connection Process
For details regarding the Multi-Unit connection process, refer to NCN GL0006 Residential Unit
Development Handbook.
3.1.3 Commercial Gas Connections
For Commercial Gas Connections, refer to Section 3.5.5.
3.2 Determining Gas Availability
To determine if gas is available to the property, please contact a gas retailer.
If gas is not outside the property but in an adjoining street, or if there is no appropriate gas
main in the vicinity, then a mains extension may be required to bring gas to the property. If
requested, a gas retailer will organise a quotation from AGA to extend the gas main to the
property.
Where a gas connection cannot readily be made because there is no direct street frontage to a
gas main (e.g., a property on a rear laneway without gas mains), refer to Section4.1.7.
6
3.3 Gas Meter Size and Diversification
GAS METER SELECTION TABLE
FOR DOMESTIC INSTALLATIONS
Correct as at September 2016
Full details can be found in the ATCO Gas Australia Technical Notice available at www.atcogas.com.au
ATCO Gas
Australia Meter
Type
capacity
Always consider gas load diversity
Typical number of gas appliances
1.25kPa 2.75kPa
AL8
8m
3
/hr
300 MJ/hr
8m
3
/hr
300 MJ/hr
Up to 4 including 2 hot water systems
AL10
10m
3
/hr
375 MJ/hr
10m
3
/hr
375 MJ/hr
5-6 including 3 hot water systems
AL12
12m
3
/hr
450 MJ/hr
25m
3
/hr
940 MJ/hr
Typically 7+