EasyManua.ls Logo

Athena 16 Series - Special Functions; Remote Setpoint Select

Athena 16 Series
38 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
16
Special
Functions

If your Series 16 controller was ordered with this option, you may select either of two setpoints for your
process. The second setpoint can be enabled only by an external switch or signal, according to your
ordering specifications. The "F2" LED on the front panel will illuminate when a second setpoint is selected. If
you do not know how your Series 16 was configured, refer to the ordering code shown later in this manual.
Option Part # Description
40 External switch wired to terminals 6 and 7
Switch Open: Normal operation, first setpoint enabled
Switch Closed: Second setpoint enabled
Setpoint Adjustments: Made from front panel
41 External switch wired to terminals 6 and 7
Switch Closed: Normal operation, first setpoint enabled
Switch Open: Second setpoint enabled
Setpoint Adjustments: Made from front panel
42 0-5 Vdc signal at pins 6 and 7
0 Vdc: First setpoint enabled
5 Vdc: Second setpoint enabled
Setpoint Adjustments: Made from front panel
Maximum Input Impedance: 400 ohms @ +5 Vdc , 5 mA
. Wiring Diagram for Remote Setpoint Select Option

Related product manuals