EasyManua.ls Logo

Atlantic alfea extensa + - 3.4.6 Pump down operation

Atlantic alfea extensa +
92 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3.4.6 Pump down operation (Refrigerant collecting
operation) outdoor unit
" Ensure that the general electrical power
supply has been cut off before starting any
repair work.
"
Stored energy: after disconnecting power
supplies wait 1 minute before accessing the
internal parts of the equipment.
Perform the following procedures to collect the
refrigerant.
- 1- Turn OFF the start/stop switch
(ref. 3, gure 10, page 11). Disconnect the outdoor
units power supply.
- 2- Remove the front panel. Open the power control
box. Then turn ON the DIP SW1 on the interface
board,
- 3- Reconnect the power supply. Turn ON the start/
stop switch.(Green and Red LED on the board start
ashing ; 1 sec. on / 1 sec. off repeated). The outdoor
unit begins cooling operation about 3 minutes after
switching ON.
- 4- Rapidly: Set the parameter 7700 (Relay output
QX1) to ON. => The pump works normally.
Reminder: Press OK. Hold on the key
for 3s
and select the level of access* used with the aid
of the knob . Conrm with the key OK.
* Choose “Specialist” level / Inputs / outputs test.
- 5- Close the liquid valve on the outdoor unit 30 s
maximum after operation starts.
- 6- Close the gas valve on the outdoor unit as soon as
the pressure is lower 0.02 bar relative reading on the
Manifold or 1-2 minutes after closing the liquid valve,
while the outdoor unit keeps running.
- 7- Disconnect the power supply.
- 8- The refrigerant collecting operation is over.
Remarks:
- The pump down operation cannot be activated even if
DIP SW1 is changed while heat pump's power is ON.
- Do not forget to turn back DIP SW1 on the interface
board to OFF, after the pump down operation has
been completed.
- Select the "AUTO" heating mode.
- When the pump down operation is repeated,
temporarily turn OFF the start/stop switch after opening
the closed valves (both liquid and gas).
Interface card
LED2
(green)
LED1
(red)
OFF
ON
gure 27 - Location of DIP switches and LED
on the hydraulic unit interface card
Installation and operation manual "1734 - EN"
Heat pump air/water split 1 service alféa extensa +
- 28 -

Table of Contents

Related product manuals